Wiring configuration | 1P2W, 1P3W, 3P3W, 3P4W | |
---|---|---|
Measurements and parameters |
Ior : Leakage current (Trms) with resistive components only Io : Leakage current (Trms) with basic wave of 50/60Hz only Iom : Leakage current (Trms) including harmonic components V : Reference voltage (Trms) with basic wave of 50/60Hz only Vm : Reference voltage (Trms) including harmonic components R : Insulation resistance, Frequency(Hz), Phase angle(θ) |
|
Other functions | Digital output, Print screen, Backlight, Data hold | |
Recording Interval | 200/400ms/1/5/15/30s/1/5/15/30m/1/2hours | |
Ior | ||
Range | 10.000/100.00/1000.0mA/10.000A/AUTO | |
Accuracy | For reference voltages of sine wave 40 – 70Hz and 90V Trms or higher, ±0.2%rdg±0.2%f.s. + clamp sensor amplitude accuracy + error of phase accuracy* (phase error) * add ±2.0%rdg to measured Io value when using Ior leakage clamp sensor. (θ: within the accuracy of reference voltage/ current phase difference ±1.0°) |
|
Allowable input | 1% – 110% (Trms) of each range, and 200% (peak) of the range | |
Display range | 0.15% – 130% (display “0” for less than 0.15%, “OL” if the range is exceeded) | |
Io *Range, Allowable input and Display Range are the same as Ior . | ||
Accuracy | ±0.2%rdg±0.2%f.s.+ clamp sensor amplitude accuracy | |
Iom *Range, Allowable input and Display Range are the same as Ior . | ||
Accuracy | ±0.2%rdg±0.2%f.s.+ clamp sensor amplitude accuracy | |
Measurement method |
Sampling speed 40.96ksps (every 24.4μs), gapless, calculate Trms values every 200ms. | |
Voltage | ||
Range | 1000.0V | |
Accuracy | ±0.2%rdg±0.2%f.s. * for waveforms of sine wave 40 – 70Hz | |
Allowable input | 10 – 1000V Trms, and 2000V peak | |
Display range | 0.9 – 1100.0V Trms (display “0” for less than 0.9V, “OL” if the range is exceeded) | |
Phase angle(θ) | ||
Display range | 0.0 – ±180.0° (regarding the phase of reference voltage as 0.0°) | |
Accuracy | Within ±0.5° for the inputs of 10% or higher of leakage current range, sine wave 40 – 70Hz, reference voltage of 90V Trms or higher. Within ±1.0° when using Ior leakage clamp sensor, and Within ±0.5°+ clamp sensor accuracy when using general purpose clamp sensor. |
|
Frequency meter range | 40 – 70Hz | |
External supply | AC100 – 240V(50/60Hz) 7.5VA max | |
Power source | LR6(AA)(1.5V) × 6 (Battery life approx. 11h) | |
Display / update period | 160 × 160dots, FSTN monochrome display / 500ms | |
PC card interface | SD card (2GB) *standard accessory | |
Communication interface |
USB | |
Temperature and humidity range |
23±5°C, relative humidity 85% or less(no condensation) | |
Operating temperature and humidity range |
-10 – 50°C, relative humidity 85% or less(no condensation) | |
Storage temperature and humidity range |
-20 – 60°C, relative humidity 85% or less(no condensation) | |
Applicable Standards | IEC 61010-1 CAT Ⅳ 300V / CAT Ⅲ 600V Pollution degree 2 IEC 61010-2-030 , IEC 61010-031 , IEC 61326 |
|
Dimension | 165(L) × 115(W) × 57(D)mm | |
Weight | Approx. 680g (including batteries) | |
Accessories | 7273 (Voltage test lead) 8262 (AC adapter) 7278 (Earth cable) 7219 (USB cable) 8326-02 (SD card [2GB]) 9125 (Carrying case) Instruction manual, Cable marker, Software installation manual LR6(AA) × 6 KEW Windows for KEW 5050(PC software) |
|
Optional Accessories | 8177/8178 (Ior Leakage current Clamp Sensor) 8329 (Power supply adapter) 8121/8122/8123/8124/8125/8126/8127/8128 (Load current Clamp Sensor)* 8130/8133 (Flexible Clamp Sensor)* 8146/8147/8148 (Leakage & Load current clamp sensors)* |
Shows insulation resistance (R) values determined by the following formula.
V: Reference voltage/ Ior: Leakage current
Displayed value is just for reference since the measurement method differs from insulation resistance testers and may not be consistent with each other.
* Cannot be used for Ior measurement.
Accessories/Optional Accessories /Related Products
MODEL 7219
MODEL 7273
MODEL 7278
MODEL 8262
MODEL 8326-02
MODEL 9125
MODEL 8177
MODEL 8178
MODEL 8329
MODEL 8121
MODEL 8122
MODEL 8123
MODEL 8124
MODEL 8125
MODEL 8126
MODEL 8127
MODEL 8128
KEW 8130
KEW 8133
KEW 8146
KEW 8147
KEW 8148
Reviews