Voltage Test | |
---|---|
Voltage Range | 12 – 690V AC/DC |
Nominal Voltage | 12/24/50/120/230/400/690V AC (16 – 400Hz), DC (±) |
Tolerance | Light on at more than: |
(Threshold Voltage) | 7±3V (12V LED) 18±3V (24V LED) 37.5±4V (50V LED) 75%±5% of nominal voltage (120/230/400/690V LED) |
Response Time | <0.6s at 100% of each nominal voltage |
Peak Current | ls<3.5mA (at 690V) |
Measurement Duty | 30s ON (operation time) 240s OFF (recovery time) |
Single-pole Phase Test | |
Voltage Range | 100 – 690V AC (50/60Hz) |
Phase Rotation Test | |
System | Three-phase 4-wire system 200 – 690V phase-to-phase AC (50/60Hz) |
Phase Range | 120±5 degree |
Continuity Test | |
Detection Range | 0 – 400kΩ+50% |
Test Current | Approx. 1.5μA (battery 3V, 0Ω) |
Applicable standards | IEC 61243-3, IEC 61010-1, IEC 61557-7 CAT Ⅲ 690V / CAT Ⅳ 600V Pollution degree 2 |
---|---|
IP Rating | IP65 (IEC 60529) |
Operating temperature and humidity range | -15 – 55°C, relative humidity 85% or less (no condensation) |
Storage temperature and humidity range | -20 – 70°C, relative humidity 85% or less (no condensation) |
Power source | LR03 (AAA) 1.5V×2 |
Dimension | 246(L)×64(W)×26(D) mm |
Weight | Approx. 190g (including batteries) |
Accessories | LR03 (AAA) 1.5V×2, KTA01 (4mm metal tips [2pcs/set]), KTA02 (4mm rubber caps [2pcs/set]), Instruction manual |
Reviews
There are no reviews yet.