Insulation Resistance
Test voltage | 250/500/1000V |
---|---|
Measuring ranges<br>(Mid-scale value) | 100/200/400MΩ (1/2/4MΩ) |
Output voltage on open circuit | Rated test voltage+20%, -0% |
Nominal current | 1mA DC min. |
Output short circuit current | Approx. 1.3 mA DC |
Accuracy | 0.1 – 10/0.2 – 20/0.4 – 40MΩ (Accuracy Guaranteed Ranges) ±5% of indicated value |
Continuity
Measuring ranges<br>(Mid-scale value) | 2/20Ω (1/10Ω) |
---|---|
Output voltage on open circuit | 4 – 9V DC |
Measuring current | 200mA DC min |
Accuracy | ±3% of scale length |
General
Safety Standard | IEC 61010-1 CAT III 300V Pollution Degree 2 IEC 61010-2-034, IEC 61557-1,2,4 |
---|---|
IP Rating | IEC 60529-IP54 |
EMC Standard | IEC 61326-1 |
Power source | R6 (AA) (1.5V) × 6 |
Dimension | 167(L) × 185(W) × 89(D)mm |
Weight | Approx. 860g |
Accessories | 7122B (Test leads) Pouch for test leads 9074 (Cord case) 8923 (Fuse[0.5A/600V]) × 1 (included), 1 (spare) R6 (AA) × 6 9121 (Shoulder Strap) Instruction Manual |
Accessories/Optional Accessories /Related Products

MODEL 7122B

MODEL 9074

MODEL 8923

MODEL 9121
Reviews
There are no reviews yet.