Continuity Testing | ||
---|---|---|
Measuring Range | 20/200Ω (Auto-Ranging) | |
Open Circuit Voltage | > 6V | |
Short Circuit Current | > 200mA | |
Accuracy | ±(3%rdg + 3dgt) | |
Insulation Resistance Testing | ||
Measuring Range | 20/200MΩ (Auto-Ranging) | |
Test Voltage | 500/1000V | |
Open Circuit Voltage | +20% – 0% | |
Rated Current | > 1mA | |
Accuracy | ± (3%rdg + 3dgt) | |
Loop Impedance Testing | ||
Impedance Range | 20/2000Ω | |
Rated Voltage | 230V + 10% – 15%(50Hz) | |
Normal Test Current | 20Ω:25A/10ms 2000Ω:15mA/350ms max. |
|
Accuracy | ±(3%rdg + 8dgt) | |
RCD Testing | ||
Test Current (Test Current Duration) |
x1/2, x1 | 10, 30, 100, 300, 500mA (2000ms) |
Fast | 150mA (50ms) | |
DC | 10, 30, 100, 300mA (2000ms), 500mA (200ms) | |
Auto Ramp | Goes up by 10% from 20% to 110% of IΔn. 300ms×10 | |
Rated Voltage | 230V + 10% – 15% [50Hz] | |
Accuracy | Test Current | x1/2: -8%-2% x1, FAST: +2%+8% DC: ±10% Auto Ramp: ±4% |
Trip Time | ±(1%rdg + 3dgt) | |
Uc Testing | ||
Measuring Range | 100V | |
Rated Voltage | 230V + 10% – 15% (50Hz) | |
Test Current | 5mA at IΔn = 10mA 15mA at IΔn = 30/100mA 150mA at IΔn = 300/500mA |
|
Accuracy | +5% to +15%rdg±8dgt |
Safety Standard | IEC 61010-1 CAT III 300V Pollution Degree 2 IEC 61010-2-034, IEC 61557-1, 2, 3, 4, 6, 10, IEC 60529 (IP40) |
---|---|
Power source | R6/LR6 × 8 |
Dimension | 115(L) × 175(W) × 86(D)mm |
Weight | Approx. 840g |
Accessories | 7122B (Test leads) KAMP10 (Test lead with IEC connector)*1 8923 (Fuse[0.5A/600V] × 1 (included), 1 (spare) 9092 (Cord case) 9121 (Shoulder strap) Shoulder pad Instruction manual R6(AA) × 8 |
Optional Accessories | 7133B (Distribution board test leads) 8212-USB (USB adapter) |
Accessories/Optional Accessories /Related Products
MODEL 7122B
MODEL KAMP10
MODEL 7133B (OMA DIEC)
MODEL 8212-USB
Reviews
There are no reviews yet.